This "calculator" is provided for comparison purposes only, and
the resulting pressure drop can be dramatically different in actual field
conditions.
Note that the pressure drop calculated above is based on liquid media with
the specific gravity of water (1.0) and the viscosity of water (1.0 centistoke).
Even if your liquid has the same properties as water, other factors can impact
the actual pressure drop.
The results above and the formulas
provided by Plast-O-Matic Valves, Inc. are offered only for comparing the
characteristics of thermoplastic valves, and are not for determining actual
performance or for system design.
If you would like to determine other aspects of the pressure drop equation,
for instance: What is the minimum Cv that will result in no more than a 10
psi pressure drop at 20 GPM? or, for instance, How much flow do I need to
have less than 3 psi pressure drop with a .8 Cv?, your best bet is to use
the actual formulas, which are shown here, or described in detail on our pressure
loss and flow equation page. Even if you have used the calculator above, you
will likely find the information on this link helpful.
Copyright©
Plast-O-Matic Valves, Inc. 2002
Cv Factors Table Entries
| AIR
SHUT-OFF VALVES & DIAPHRAGM VALVES |
| BLT Series Shutoff Valves |
|
|
| Part Number |
Size |
Cv Factor |
| BLT050 |
½" |
3.6 |
| BSD/BSDA Series Compact Valves |
|
|
| Part Number |
Size |
Cv Factor |
| BSD025 |
¼" |
1.1 |
| BSD050 |
½" |
3.4 |
| BSD075 |
¾" |
5.8 |
| BSD100 |
1" |
6.3 |
| BSD150 |
1½" |
17.0 |
| Part Number |
Size |
Cv Factor |
| BSDA025 |
¼" |
1.1 |
| BSDA050 |
½" |
3.4 |
| BSDA075 |
¾" |
5.8 |
| BSDA100 |
1" |
6.3 |
| BSDA150 |
1½" |
17.0 |
| BSR Series Balanced Shutoff Valves |
|
|
| Part Number |
Size |
Cv Factor |
| BSR050 |
½" |
3.0 |
| BSR075 |
¾" |
8.0 |
| BST Series Shutoff Valves |
|
|
| Part Number |
Size |
Cv Factor |
| BST050 |
½" |
3.6 |
| EAT/ELT/EST Series Shutoff Valves |
|
|
| Part Number |
Size |
Cv Factor |
| EAT075 |
¾" |
8.5 |
| EAT100 |
1" |
15.0 |
| EAT125 |
1¼" |
24.0 |
| EAT150 |
1½" |
33.0 |
| EAT200 |
2 |
60.0 |
| Part Number |
Size |
Cv Factor |
| ELT075 |
¾" |
8.5 |
| ELT100 |
1" |
15.0 |
| ELT125 |
1¼" |
24.0 |
| ELT150 |
1½" |
33.0 |
| ELT200 |
2 |
60.0 |
| Part Number |
Size |
Cv Factor |
| EST075NC |
¾" |
8.5 |
| EST100NC |
1" |
15.0 |
| EST125NC |
1¼" |
24.0 |
| EST150NC |
1½" |
33.0 |
| EST200NC |
2 |
60.0 |
DIVERTER
VALVES
(See also 3-way Ball Valves and 3-way Solenoid Valves) |
| BFS Series -- NORMALLY OPEN |
|
|
| Part Number |
Size |
Cv Factor |
| BFS050 |
½" |
3.6 |
| BFS Series -- NORMALLY CLOSED |
|
|
| Part Number |
Size |
Cv Factor |
| BFS050 |
½" |
2.5 |
| F Series -- NORMALLY OPEN |
|
|
| Part Number |
Size |
Cv Factor |
| F075 |
¾" |
12.2 |
| F100 |
1" |
19.2 |
| F125 |
1¼" |
34.5 |
| F150 |
1½" |
47.5 |
| F200 |
2 |
79.0 |
| F Series -- NORMALLY CLOSED |
|
|
| Part Number |
Size |
Cv Factor |
| F075 |
¾" |
7.3 |
| F100 |
1" |
11.5 |
| F125 |
1¼" |
20.7 |
| F150 |
1½" |
28.5 |
| F200 |
2 |
47.5 |
| TUCA Series -- Compact 3-way (Diverter) Valves |
|
|
| Part Number |
Size |
Cv Factor |
| TUCA025V |
¼" |
0.4 |
| TUCA050V |
½" |
0.4 |
| GAUGE
GUARDS |
| Series GGMU, Ultra-Pure Gauge Guard |
|
|
| Part Number |
Size |
Cv Factor |
| GGMUV050 |
½" |
10.0 |
| GGMUV075 |
¾" |
20.0 |
| GGMUV100 |
1" |
40.0 |
| GGMUV150 |
1½" |
100.0 |
| GGMUV200 |
2 |
120.0 |
| BALL
VALVES |
| 2-way Ball Valves, including all actuated versions |
|
|
| Part Number |
Size |
Cv Factor |
| MBV050 |
½" |
10.0 |
| MBV075 |
¾" |
20.0 |
| MBV100 |
1" |
40.0 |
| MBV125 |
1¼" |
80.0 |
| MBV150 |
1½" |
100.0 |
| MBV200 |
2 |
120.0 |
| 3-way Ball Valves, including all actuated versions |
|
|
| Part Number |
Size |
Cv Factor |
| TMBV050 |
½" |
4.0 |
| TMBV075 |
¾" |
8.0 |
| TMBV100 |
1" |
13.0 |
| TMBV150 |
1½" |
38.0 |
| TMBV200 |
2 |
39.0 |
| MANUAL
SHUT-OFF VALVES |
| MFR Series |
|
|
| Part Number |
Size |
Cv Factor |
| MFR050 |
½" |
3.0 |
| MFR075 |
¾" |
8.0 |
| SOLENOID VALVES |
| EASYM/EASM with AC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYM2V8W20 |
¼" |
1.1 |
| EASYM4V8W20 |
½" |
1.1 |
| EASM4V12W20 |
½" |
2.1 |
| EASM5V16W20 |
¾" |
3.1 |
| EASM6V22W20 |
1" |
5.5 |
| EASM4V12G58 |
½" |
2.3 |
| EASM5V16G58 |
¾" |
3.4 |
| EASM6V22G58 |
1" |
6.2 |
| EASYM/EASM with DC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYM2V8W20 |
¼" |
1.1 |
| EASYM4V8W20 |
½" |
1.1 |
| EASM4V12W20 |
½" |
1.6 |
| EASM5V16W20 |
¾" |
2.2 |
| EASM6V22W20 |
1" |
4.0 |
| EASYMD/EASMD with AC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYMD2EP14W20 |
¼" |
1.1 |
| EASYMD4EP14W20 |
½" |
1.1 |
| EASMD4EP14W20 |
½" |
2.3 |
| EASMD5EP16W20 |
¾" |
3.1 |
| EASMD6EP22W20 |
1" |
5.5 |
| EASMD4EP14G58 |
½" |
2.3 |
| EASMD5EP16G58 |
¾" |
3.1 |
| EASMD6EP22G58 |
1" |
5.5 |
| EASYMD/EASMD with DC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYMD2EP14W20 |
¼" |
1.1 |
| EASYMD4EP14W20 |
½" |
1.1 |
| EASMD4EP14W20 |
½" |
1.8 |
| EASMD5EP16W20 |
¾" |
2.2 |
| EASMD6EP22W20 |
1" |
4.0 |
| EASYMT/EASMT PTFE Bellows with AC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYMT2V12W20 |
¼" |
1.1 |
| EASYMT4V12W20 |
½" |
1.1 |
| EASMT4V12W20 |
½" |
2.1 |
| EASMT5V16W20 |
¾" |
3.1 |
| EASMT6V22W20 |
1" |
4.6 |
| EASMT6V14W20 |
1" |
3.6 |
| EASMT4V12G58 |
½" |
2.3 |
| EASMT5V16G58 |
¾" |
3.4 |
| EASMT6V22G58 |
1" |
4.7 |
| EASYMT/EASMT PTFE Bellows with DC COILS |
|
|
| Part Number |
Size |
Cv Factor |
| EASYMT2V12W20 |
¼" |
1.1 |
| EASYMT4V12W20 |
½" |
1.1 |
| EASMT4V12W20 |
½" |
1.6 |
| EASMT5V16W20 |
¾" |
2.2 |
| EASMT6V22W20 |
1" |
4.0 |
| EASMT6V14W20 |
1" |
2.9 |
| EASMT4V12G58 |
½" |
N/A |
| EASMT5V16G58 |
¾" |
N/A |
| EASMT6V22G58 |
1" |
N/A |
| EAST Compact PTFE Bellows Valves |
|
|
| Part Number |
Size |
Cv Factor |
| EAST2V6W11 |
¼" |
0.5 |
| EAST2V8W11 |
¼" |
0.8 |
| EAST4V6W11 |
½" |
0.5 |
| EAST4V8W11 |
½" |
0.8 |
| EAST-NO Normally Open Solenoid Valves |
|
|
| Part Number |
Size |
Cv Factor |
| EASY2B8W20-NO |
¼" |
1.1 |
| EASY4B8W20-NO |
½" |
1.1 |
| PS Series Pilot-Operated/PTFE Bellows Solenoid Valves |
|
|
| Part Number |
Size |
Cv Factor |
| PS050 |
½" |
5.2 |
| PS075 |
¾" |
7.60 |
| PS100 |
1" |
9.5 |
| PS150 |
1½" |
28.0 |
| PS200 |
2" |
35.0 |
| PS300 |
3" |
80.0 |
| THP Series 3-Way Solenoid Valves |
|
|
| Part Number |
Size |
Cv Factor |
| THP2V4W20 |
¼" |
0.31 |
| THP4V4W20 |
½" |
0.31 |
| THP2V6W20 |
¼" |
0.52 |
| THP4V6W20 |
½" |
0.52 |
| THP2V8W20 |
¼" |
0.61 |
| THP4V8W20 |
½" |
0.61 |
| TUC Series 3-Way Solenoid Valves |
|
|
| Part Number |
Size |
Cv Factor |
| TUC2V3W20-PV |
¼" |
0.22 |
| TUC4V3W20-PV |
½" |
0.22 |
| TUC2V4W20-PV |
¼" |
0.31 |
| TUC4V4W20-PV |
½" |
0.31 |
|
TUC2V8W20-PV
|
¼" |
0.40 |
| TUC4V8W20-PV |
½" |
0.40 |
| WC Series Wetted Core Solenoid Valves |
|
|
| Part Number |
Size |
Cv Factor |
| WC4V6W11-PP |
½" |
0.40 |
Plast-O-Matic Valves, Inc.
1384 Pompton Avenue
Cedar Grove, NJ 07009-1095 USA
Viton® is registered trademark of DuPont Dow Elastomers,
Kynar ® is a registered trademark of Elf Atochem., Corzan tm is a trademark
of Noveon, Inc.
FAIL-DRY ® is a registered trademark of Plast-O-Matic Valves, Inc.
Copyright© 2002 Plast-O-Matic Valves, Inc.
|