Specifications for 8710 pH / ORP
Transmitter -
This has been
replaced by 8750 - take me there
This is a two wire device that transmits an
analog signal of 4 - 20 mA from input from a pH or ORP sensor.
The unit uses a Loop Power of 10 to 30
VDC. This will provide signal for a Signet or other processor controller.
Technical Data
Loop power: 10 to 30 VAC
Loop impedance: 1 @ 10W VDC,
100W @ 12VCD, 1000W @ 30 VDC
Electronics temperature range: 5 to 158o
F - 95% relative humidity
Sensor Input Signal Ranges
- pH: 0 to 14
- Temperature: -10 to 120o C
- ORP: -999 to + 1999 millivolts
Current Outputs: pH or ORP 4 - 20 mA - input
isolated
Display / Accuracy
- +/- 0.03 pH units
- +/- 3 Millville
- +/- 0.2% loop current scale
Minimum span (for 4 - 20 mA signal): 2.0
pH units - 120 Millville
Materials of Enclosure:
- glass filled polypropylene - silicon rubber
keypad and gasket
- Polycarbonate window
- NEMA 4X/IP65
Quality Standard: CE
Installation of
Compak Transmitter
Dimensions
of Compak Transmitter
Instruction Sheets -
All - PDF file format
|